C106 Keypad
11
Electric Lock Release
When installing lock releases please allow a little movement on the door as
operation will be impaired if fitted too tightly.
The C106 Keypad provides two alternative pairs of connections for direct
connection of an electric lock releases:-
‘FAIL SECR’ : Use these connections for ‘Fail-Secure’ lock releases. These
devices require power to release the lock and will secure the door in the event
of power failure. These are the most commonly used lock releases.
‘FAIL SAFE’ : Use these connections for ‘Fail-Safe’ lock releases and magnetic
locks. Both of these devices require continuous power to lock the door and will
release the door if power fails.
Note ‘Fail Safe’ lock releases are DC only
These outputs are rated at the input voltage (12V D, 12V A) with a maximum
current consumption of 0.5A.
C106 Keypad
12
High Current Lock Releases
For a lock release or a magnetic lock rated higher than 0.5A an additional power
supply will be required. In addition a relay must be used to interface with the
C106 Keypad.
The relay contacts, or the lock-release, must be fitted with a suitable suppression
device to prevent voltage transient and electromagnetic interference being
generated by the coil of the lock release. (Refer to manufacturer for further
advice).
Consideration should be given to the problem of a voltage drop at the lock
release. Please refer to the manufacturer of the particular lock release for
information on suitable cable length versus thickness and power supply rating.
High Current Lock Release